In this Paper, the lightning performance of the 150 kV transmission line in west Sumatera, Indoensia, is studied in details, showing that the lightning trip-out rate depends on the tower-footing resistance and the length of an arcing horn gap. the observed trip-out rate higher than 20 trip-outs/100km-year is in good agreement with the resulkt of the simulation by the IEEE FLASH program by using the so-callled impulse resistance. the dependency of the trip-out rate on the arm location fairly well agrees eith the rate estimated by the IEEE metrhod too.


Ketersediaan

Tidak ada salinan data


Informasi Detil

Judul Seri
Lightning Trip-Out of 150 kV Transmission Line: a Case Study
No. Panggil
620.005
Penerbit Praise Worthy Prize : Japan.,